MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair concrete at entrance to dock hoistway--tripping hazard
|
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)1
|
|
|
Install No Passenger sign in car
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
All electrical covers shall be installed when job is complete.
|
2/19/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
x
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
2/19/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
2/19/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Battery lowering shall work.
|
2/19/2024
|