Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Fire extinguisher needed in machine room | 11/14/2023 | |
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lights below 19fc | 11/14/2023 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Battery backup not working | 11/14/2023 | |
A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | x | In case of fire don't use elevator signage needed | 11/14/2023 |