A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Machine disconnect workspace blocked by light disconnect and fire panel.
|
11/9/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag)
|
x
|
x
|
Means of two way communication are inoperable and shall be repaired or replaced.
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Machine room door shall be self-closing and self-locking.
|
11/9/2023
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire penetrations in hoistway shall be repaired.
|
11/9/2023
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
3.14
|
x
|
|
Car lighting shall work.
|
11/9/2023
|