Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Item 2.27.3.2.1(b) Heat Device & Smoke innating shall be functional at the Elevator Main Line Disconnect & 110 Elevator Disconnect in the Electrical Control Room at the Main Level, Did not Red Tag Elevator locked out by Elevator Contractor Must Reinspect.. 1/4/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Fire Extinguisher shall be provided @ the Control Room on Level 3. 1/4/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Item 2.1.6.2(a) Projection inside the elevator hoistway (pit) shall not be greater than 4 inches. Projection is 6.5 inches which will require a 75 degree bevel 1/4/2024