Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Top entry header needs grout or sealed 2/28/2024
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 2.1.1 x Bottom floor entrance needs grout or sealed 2/28/2024
A17.1-2016 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.14.1.7.1 x Cartop needs railing. Clearances over 12 inches. 2/28/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Sump pump needs cover 2/28/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) x x Phone not working. Faulty programming 2/28/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2 through 2.27.8 Firefighter Service x x Fire service not finished and connected to elevator 2/28/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x x Need shunt trip from pit sprinkler 2/28/2024