                        A17.1-2016 : Elevators
                     | 
                    
                        3.17 - Door and gate equipment
                     | 
                    
                        2.11
                     | 
                    
                     | 
                    
                     | 
                    
                        Door closer not working at Floor LL (side).
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        1.9 - Power closing of doors or gates
                     | 
                    
                        2.13.4.2.2
                     | 
                    
                     | 
                    
                     | 
                    
                        Minimum door close speeds not on door operator data tag. (ref 2.13.4.2.4 not selectable on dropdown)
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
                     | 
                    
                        8.6.4.19.17 Earthquake Operation
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Seismic displacement device (ring and string) not working.
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        1.17 - Standby power operation
                     | 
                    
                        8.11.2.1.1(q)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency power not tested.
                     | 
                    
                        
                     |