Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.1.6.1 - There is no lockable disconnect.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.10.7 - No slack chain switch or SOS switch.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.11 - Unit shall have two-way communication and audible alarm which shall be on back up battery when power is removed.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.13 - Shall have code data tags.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.3.6 - Guiding members shall be enclosed.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.3.8 - Controller pump unit suspended from ceiling. There is no permanent access under dropped ceiling.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
2.6.7 - Pictograph "In Case of Fire, do not use lift" at each landing.
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
10.1.5 Installation Placed Out of Service
|
x
|
x
|
Decommissioned unit
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
x
|
|
There is no port to test the relief pressure. Relief pressure shall be tested.
|
|