Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.1.6.1 - There is no lockable disconnect.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.10.7 - No slack chain switch or SOS switch.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.11 - Unit shall have two-way communication and audible alarm which shall be on back up battery when power is removed.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.13 - Shall have code data tags.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.3.6 - Guiding members shall be enclosed.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.3.8 - Controller pump unit suspended from ceiling. There is no permanent access under dropped ceiling.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x 2.6.7 - Pictograph "In Case of Fire, do not use lift" at each landing.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts 10.1.5 Installation Placed Out of Service x x Decommissioned unit
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x There is no port to test the relief pressure. Relief pressure shall be tested.