A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
Sills and flooring shall be relatively coplanar. Original hoistway sill extends above flooring by as much as 3/4".
|
7/19/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Communication loss monitoring system shall work.
|
7/19/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Rescue phone shall be installed and work.
|
7/19/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work (with and w/o main power) and give proper location.
|
7/19/2023
|
A17.1-2016 : Elevators
|
3.7 - Car leveling and anticreep devices
|
2.26.1.6
|
x
|
|
Car stops 2" low on most floors.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Original machine room door to be permanently bolted closed from inside, as it now opens to a 15 foot falling hazard.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Overhead Machine space lighting shall be at least 19fc. It is currently at 5fc.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Machine room shall have proper fire extinguisher. Current tested and tagged ABC type extinguisher.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Sprinkler pipe running across pit floor creates a tripping hazard. Relocate to remove hazard.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
x
|
|
Label all machine space components with elevator identifier including: machine, controllers, disconnects, governor, cartop, etc.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Basement electrical disconnect room shall have disconnects and transformer arranged to be code compliant.
|
7/19/2023
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.9
|
x
|
|
Code year data tag shall be installed on controller.
|
7/19/2023
|
A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
x
|
|
Install toe kick guard at rear of car below handrail.
|
7/19/2023
|
A17.1-2016 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
x
|
|
Hoistway doors shall have floor identifying numbers on hoistway side.
|
7/19/2023
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Concrete projection at top of hoistway/TSU/Drive shall be moved to allow proper running clearances of cartop. The remaining exposed portion of concrete projection shall be properly beveled.
|
7/19/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit space lighting shall be at least 19fc. It is currently 9fc.
|
7/19/2023
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.4
|
x
|
|
2.4.5 - Install counterweight maximum run-by signage in pit.
|
7/19/2023
|