Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 x Sills and flooring shall be relatively coplanar. Original hoistway sill extends above flooring by as much as 3/4". 7/19/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Communication loss monitoring system shall work. 7/19/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Rescue phone shall be installed and work. 7/19/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work (with and w/o main power) and give proper location. 7/19/2023
A17.1-2016 : Elevators 3.7 - Car leveling and anticreep devices 2.26.1.6 x Car stops 2" low on most floors. 7/19/2023
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Original machine room door to be permanently bolted closed from inside, as it now opens to a 15 foot falling hazard. 7/19/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Overhead Machine space lighting shall be at least 19fc. It is currently at 5fc. 7/19/2023
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Machine room shall have proper fire extinguisher. Current tested and tagged ABC type extinguisher. 7/19/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Sprinkler pipe running across pit floor creates a tripping hazard. Relocate to remove hazard. 7/19/2023
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 x Label all machine space components with elevator identifier including: machine, controllers, disconnects, governor, cartop, etc. 7/19/2023
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Basement electrical disconnect room shall have disconnects and transformer arranged to be code compliant. 7/19/2023
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x Code year data tag shall be installed on controller. 7/19/2023
A17.1-2016 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.10.2.3 Toe Board x Install toe kick guard at rear of car below handrail. 7/19/2023
A17.1-2016 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 x Hoistway doors shall have floor identifying numbers on hoistway side. 7/19/2023
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Concrete projection at top of hoistway/TSU/Drive shall be moved to allow proper running clearances of cartop. The remaining exposed portion of concrete projection shall be properly beveled. 7/19/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit space lighting shall be at least 19fc. It is currently 9fc. 7/19/2023
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.4 x 2.4.5 - Install counterweight maximum run-by signage in pit. 7/19/2023