Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 A permanent and unobstructed means of access to elevator machine rooms and overhead machinery spaces shall be provided and maintained. The machine room door was blocked by material being stored directly in front of it when we arrived for the inspection. 4/2/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation A record of findings for firefighters' service operation, tested monthly as required with identification of the person(s) that performed the operation and the date shall be available on site. No entries to the MCP have been recorded since the elevator was turned over for service last year. 4/2/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. 4/2/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Machine room keys shall be kept on the premises in a location readily accessible to elevator personnel. The keys weren't on site and took more than an hour to locate. 4/2/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Where sprinklers are located in the bottom of the hoistway (the pit), fire detection devices shall be installed in the pit in accordance with Chapter 17. NFPA 72 - 21.3.7(2). Smoke detectors shall not be installed in elevator pits to initiate elevator recall unless the smoke detector is listed for the environment. NFPA 21.3.8. If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted. Note: The heat detector in the pit shall be replaced with an automatic fire detection device designed to work in wet areas. 2/20/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x A17.1 Interpretation 10-1496 - The sump control shall not be located in the elevator hoistway or in any elevator machinery spaces. If no suitable place is available, a variance with the State of Missouri can be applied for. 2/20/2024