Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service issue after normal phase 2 operation elevator will not return to Phase 1 or normal. Remains in Phase 2 even after duplex is reset successfully to normal. Reinspection required in 14 calendar days or will be removed from service 10/29/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Unable to communicate with emergency personnel over phone. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide State equipment sticker on controller 11/5/2020