ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
Alarm inoperable on battery. Red-tagged, Re-inspection required
|
8/13/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
Emergency communication inoperable. Red-tagged, Re-inspection required
|
8/13/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Need to post a current certificate
|
11/3/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certificate in machine room
|
6/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.9
|
|
|
Provide proper code data tag conforming to code.
|
11/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair phone in car
|
5/20/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.3 Provide Auxiliary Lighting
|
x
|
x
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Red-tagged, Re-inspection required
|
8/13/2024
|