A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
2.2.5.1 - The pit light shall be operational and shall not be less than 10fc at the pit floor level; currently 2fc at ladder.
|
9/14/2023
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
2.7.5.1 - Machine/controller space light fixture to be permanently wired and covers installed.
|
9/14/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Fire alarm initiating devices (FAID) shall all work properly and initiate proper elevator recall. Multiple devices either did not initiate recall or shunt as needed. Retesting of all FAID required.
|
9/14/2023
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
NEC 110.26 - Disconnects do not meet 30" rule and are not co-planer.
|
9/14/2023
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
x
|
|
The pit shall be kept clean. Remove the excess debris.
|
9/14/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current operating certificate shall be posted in machine room.
|
4/16/2025
|