Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current operating certificate shall be posted in machine room. 4/16/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Fire alarm initiating devices (FAID) shall all work properly and initiate proper elevator recall. Multiple devices either did not initiate recall or shunt as needed. Retesting of all FAID required. 9/14/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No 2.7.5.1 - Machine/controller space light fixture to be permanently wired and covers installed. 9/14/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No NEC 110.26 - Disconnects do not meet 30" rule and are not co-planer. 9/14/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Yes No The pit shall be kept clean. Remove the excess debris. 9/14/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No 2.2.5.1 - The pit light shall be operational and shall not be less than 10fc at the pit floor level; currently 2fc at ladder. 9/14/2023