Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x 2.2.5.1 - The pit light shall be operational and shall not be less than 10fc at the pit floor level; currently 2fc at ladder. 9/14/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Fire alarm initiating devices (FAID) shall all work properly and initiate proper elevator recall. Multiple devices either did not initiate recall or shunt as needed. Retesting of all FAID required. 9/14/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x NEC 110.26 - Disconnects do not meet 30" rule and are not co-planer. 9/14/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x 2.7.5.1 - Machine/controller space light fixture to be permanently wired and covers installed. 9/14/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current operating certificate shall be posted in machine room. 4/16/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x The pit shall be kept clean. Remove the excess debris. 9/14/2023