Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Disconnects and panel need proper labels. 10/17/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x NEC 110.26 - Disconnects do not meet 30" rule/not co-planer. 10/17/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x NEC 110.26 - Transformer violates disconnect workspace. Relocate. 10/17/2024
A17.1-2016 : Elevators 2.4 - Machine space 8.6.1.6.5 Fire Extinguishers x Machine space shall have proper fire extinguisher and shall have current monthly/annual test tag. 10/17/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x All materials in hoistway shall be fire resistant (exposed wood under sills). 10/17/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Pit: Fire caulk penetrations b/w drywall and horizontal concrete beams. 10/17/2024
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x Counterweight runby shall be within OEM tolerance. 10/17/2024