A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
All materials in hoistway shall be fire resistant (exposed wood under sills).
|
10/17/2024
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
Counterweight runby shall be within OEM tolerance.
|
10/17/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Disconnects and panel need proper labels.
|
10/17/2024
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.1.6.5 Fire Extinguishers
|
x
|
|
Machine space shall have proper fire extinguisher and shall have current monthly/annual test tag.
|
10/17/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
NEC 110.26 - Transformer violates disconnect workspace. Relocate.
|
10/17/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
NEC 110.26 - Disconnects do not meet 30" rule/not co-planer.
|
10/17/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Pit: Fire caulk penetrations b/w drywall and horizontal concrete beams.
|
10/17/2024
|