A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car.
|
5/8/2024
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
2.11.11.1(b) - Landing sills to be substantially flush with the floor surface of the elevator landings.
|
5/8/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Top of hoistway:(2) 4 x 4 boxes are missing KO plugs.
|
5/8/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Pit: (1) 4 x 4 box is missing KO plugs.
|
5/8/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Pit: Lighting conduit needs to be secured.
|
5/8/2024
|
A17.1-2016 : Elevators
|
3.14 - Hoistway clearances
|
2.5
|
|
|
Front door clutch shall have proper clearance to hoistway sill. Clutch is striking the hoistway sill on multiple floors.
|
4/16/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Pit sump pump cover is required.
|
5/8/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
x
|
|
2.2.4.2.4 - A clear distance of not less than 115 mm from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the ladder shall be provided.
|
5/8/2024
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.1
|
x
|
|
Phase 1 operating instruction shall be posted in hall.
|
7/7/2025
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Operating Certificate shall be posted in machine room.
|
4/16/2025
|