Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 x 2.11.11.1(b) - Landing sills to be substantially flush with the floor surface of the elevator landings. 5/8/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x 2.2.4.2.4 - A clear distance of not less than 115 mm from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the ladder shall be provided. 5/8/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car. 5/8/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Pit sump pump cover is required. 5/8/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Pit: (1) 4 x 4 box is missing KO plugs. 5/8/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Pit: Lighting conduit needs to be secured. 5/8/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Top of hoistway:(2) 4 x 4 boxes are missing KO plugs. 5/8/2024