A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.1.3
|
x
|
|
The machine room door wasn't equipped with a permanent label indicating the fire rating. The contractor drilled the door and installed a tag. The door may not have the required fire rating.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
The sump pump shall have the capacity to remove a minimum of 3,000 GPH per elevator.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
The lighting in the pit shall provide an illumination of not less than 10 fc at the pit floor.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
2.27.3.2.1 - When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1(c) of A17.1 2016 and shall be located in the pit per NFPA 72 21.3.7(2). Also, Smoke detectors shall not be installed in elevator pits to initiate elevator recall unless the smoke detector is listed for the environment per NFPA 72 2.3.8. Note(1): Exception - A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed at the bottom of the elevator hoist-way (the elevator pit), provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. Note (2): The sprinklers in the pit are required by NFPA13 8.15.5 and permitted by A17.1 2016 2.8.3.3
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
The penetration in the wall above the machine room door shall be patched with approved material.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without use of a key.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
The machine room temperature shall be kept within the manufacturers recommended range.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
All wiring in the hoistway shall be enclosed
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Penetrations on the inside of the hoistway wall where the sprinkler pipes enter shall be patched with approved material.
|
11/3/2023
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door.
|
11/3/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
The elevator manufacturer requires the overhead hoisting beam to be labeled for capacity.
|
11/3/2023
|