Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 8/8/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.14 - Hoistway clearances 2.4 Insufficient counterweight clearance to buffer with car level at top floor. Hoist ropes need to be shortened. 5/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Pit sump Pump piping valve appears to be in closed/inoperable position. Shall be kept in open position. 9/29/2020