MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
A data plate, permanently and securely attached, shall be provided in the pit, in the vicinity of the Counterweight buffer indicating Maximum designed counterweight runby.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
No
|
No
|
A record of findings for firefighters service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on site.
|
8/12/2026
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
No
|
No
|
Feeder locations for the main and lighting branch curcuits shall be marked on the disconnects.
|
8/12/2026
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.11.2.1.4(b)
|
Yes
|
No
|
Hoistway Door Safety Retainers/Fire tabs shall be installed at the bottom of all hoistway doors. Missing on 14th Floor.
|
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
No
|
No
|
Feeder locations for the main and lighting branch circuits shall be marked on the disconnects.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
No
|
No
|
A code compliant MCP and related on-site documentation shall be provided in the machine room
|
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
No
|
No
|
Car top work light does not work
|
|