Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-WAY COMMUNICATION DEVICE SHALL WORK.Voice works, Camera works, text do not.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No data plate, permanently and securely attached, shall be provided in the pit, in the vicinity of the Counterweight buffer indicating Maximum designed counterweight runby.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and related on-site documentation shall be provided in the machine room
A17.1-2016 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) No No Car top work light does not work
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 No No Feeder locations for the main and lighting branch circuits shall be marked on the disconnects.
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No Counterweight runby(5") is less than required minimum of 6".
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No A record of firefighters service operation, tested mothly as required by 8.6.11.1, with identification of the person(s) that perfomed the operation and the date shall be avaliable on site. 8/12/2026
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 No No Feeder location for the main and lighting branch circuits shall be marked on the disconnects. 8/12/2026