Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power. (Connections to be made week of 3/18/24, MUST be re-inspected before 3/31/24). 3/21/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Emergency lighting shall work. 3/21/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Door operator 4x4 box is missing cover & pit 2x4 box is missing cover, box with exposed wiring. 3/21/2024
A17.1-2016 : Elevators 3.23 - Suspension Means 2.20.2 x Suspension means shall have proper data tags. 3/21/2024