A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
The floor in the elevator cab and in front of the hall door sills shall be installed and finished.
|
12/29/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
A17.1 Interpretation 10-1496 - The sump control shall not be located in the elevator hoistway or in any elevator machinery spaces.
|
12/29/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Communication failure light and audible alarm are not functioning.
|
1/9/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
Fire service not functional. It is stuck in Phase II operation. Elevator Red Tagged.
|
1/9/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1(c) of A17.1, NFPA 72 21.3.7. Smoke detectors shall not be installed in elevator pits to initiate elevator recall unless the smoke detector is listed for the environment. If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted.
|
12/29/2023
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
2.8.2.1 - The 120vac receptable in the machine room closet shall be a GFCI.
|
12/29/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
2.8.3.3.2 - Where elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operations, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water. The shunt trip shall be activated and remove power to the elevator by activation of the heat detector next to the sprinkler by the machine room door.
|
12/29/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car telephone shall be operational.
|
12/29/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
Two-way communication device (phone) is not functioning. The emergency signaling device (audible alarm) is also not functioning. Elevator Red Tagged for no emergency communication.
|
1/9/2025
|