A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.6
|
No
|
No
|
A secondary stop switch is required for elevator pit depths over 67”, this elevator pit exceeds 67”. A secondary stop switch shall be installed in the pit and shall conform to this section.
|
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
Yes
|
No
|
Close conduit above the control room entrance
|
6/12/2025
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
Yes
|
Yes
|
Fire recall activation devices shall be tested
|
6/12/2025
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
Yes
|
No
|
Increase the machine room illumination to 19fc throughout measured at the floor
|
6/12/2025
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.1.6.5 Fire Extinguishers
|
Yes
|
No
|
Install an ABC fire extinguisher near control room exit.
|
6/12/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
No
|
No
|
The elevator pit light switch fails to turn off the pit lighting. The electrical wiring deficiency shall be corrected to operate as required.
|
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
Yes
|
No
|
The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required.
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
No
|
No
|
The machine room lighting is a motion type sensor to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the sensor deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type sensor to a conventional on/off switch.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
No
|
No
|
There is a large abandoned pipe in the elevator pit that has a substantial amount of air coming from it. Seal pipe to prevent groundwater contamination.
|
|
|
A17.1-2016 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.1(g)
|
No
|
No
|
This elevator is labeled “Food Service” which does not coincide with other units in the facility. To avoid confusion for maintenance and elevator personnel this elevator shall be labeled “113 S” and marked as such on the elevator jams, machine room, crosshead, and inside of the car.
|
|