A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Seal hoistway penetrations and non factory seams in shaft liner
|
8/12/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
|
|
2.11 Due to the addition of sprinkler heads in the elevator machine room a heat detector is required within 24 inches of every head in the machine room to activate the shunt trip and tested
|
10/11/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27
|
x
|
x
|
Due to the addition of sprinkler heads in the elevator pit a smoke detector shall be installed in the elevator pit and recall tested.
|
8/26/2024
|