Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 Due to the addition of sprinkler heads in the elevator machine room a heat detector is required within 24 inches of every head in the machine room to activate the shunt trip and tested 10/11/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27 x x Due to the addition of sprinkler heads in the elevator pit a smoke detector shall be installed in the elevator pit and recall tested. 8/26/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Seal hoistway penetrations and non factory seams in shaft liner 8/12/2024