Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Install 110 volt car lighting supply disconnect with overcurrent protection in the machine room
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Label car 110 volt supply disconnect in machine room with feed supply location.
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Machine room HVAC shall be capable of holding the machine room within manufacturer requirements for temperature and humidity.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room illumination shall be 19ft candles throughout. Measured at the floor
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room receptacle shall be a GFIC