A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
Yes
|
No
|
Vertical ladder that provides access through machine room floor has a removable grate that shall be permanently hinged to swing up and out of the way to allow access to machine room and to be lowered and used as a working area to service overspeed governor. Grate shall be notched around handhold bar to allow grate to sit flush on support channels.
|
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
Yes
|
No
|
Provide a swing gate in machine room on access opening side at machine room floor opening. Gate shall be 42 inches tall with an intermediate bar to guard floor opening. Gate shall be self closing.
|
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
Yes
|
No
|
Remove ladder mounted to wall at bottom landing that is preventing the hoistway door from fully opening.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
Yes
|
No
|
Install ladder in elevator pit. Minimum of 9 inches wide
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
Yes
|
No
|
Provide a minimum of 10 foot candles of lighting in all areas of elevator pit. Pit light switch shall be mounted a minimum of 18 inches above bottom hoistway door landing sill
|
|
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
Yes
|
No
|
Provide air conditioning in elevator machine room to keep elevator equipment at recommended temperature and humidity operating range of elevator equipment manufacturers requirements
|
|
|
A17.1-2016 : Elevators
|
2.2 - Headroom
|
2.7.4
|
Yes
|
No
|
Elevator machine room light fixture is installed at 6'-4". A clear headroom of 7 foot minimum is required in elevator machine rooms. Install low profile light fixture to maintain height requirement.
|
|