| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Install 110V car lighting supply disconnect with overcurrent protection in the machine room. Re-inspection required | ||
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room receptacles shall be a GFCI. Re-inspection required | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | x | Mainline disconnect shall be labeled with supply location. Re-inspection required |