ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.14 - Hoistway clearances
|
2.4
|
|
|
Insufficient counterweight clearance to buffer with car level at top floor. Shorten hoist ropes.
|
10/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Car Tops
|
|
|
Clean oil from top of car
|
8/4/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and document on log in machine room
|
8/4/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working
|
10/15/2021
|