Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power operation shall be tested, with weights. 9/18/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) x Emergency power jewel needs to be installed at main landing. 9/18/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Machine room floor drain is creating a tripping hazard and shall be flush to the floor or removed. 9/18/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x 1 of 2 machine room lights are not working. 9/18/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Machine room: Overhead thru piping and flex shall be removed or enclosed. 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Disconnects need feed location labels. 9/18/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Hoistway fire penetrations need to be fire caulked. 9/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Secure sump pump cover. 9/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Light switch next to rear pit light needs to be removed. 9/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x The pit shall be kept clean and free of dirt and debris. 9/18/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 3.8 x Install cover or remove unused single gang electrical box in pit. 9/18/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fire caulk pit fire penetrations. 9/18/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Need to test all FAID operations. 9/18/2024