A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency power operation shall be tested, with weights.
|
9/18/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
x
|
|
Emergency power jewel needs to be installed at main landing.
|
9/18/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
1 of 2 machine room lights are not working.
|
9/18/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Machine room: Overhead thru piping and flex shall be removed or enclosed.
|
9/18/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Hoistway fire penetrations need to be fire caulked.
|
9/18/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Secure sump pump cover.
|
9/18/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Light switch next to rear pit light needs to be removed.
|
9/18/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
x
|
|
The pit shall be kept clean and free of dirt and debris.
|
9/18/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
3.8
|
x
|
|
Install cover or remove unused single gang electrical box in pit.
|
9/18/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk pit fire penetrations.
|
9/18/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Need to test all FAID operations.
|
9/18/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Disconnects need feed location labels.
|
9/18/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Machine room floor drain is creating a tripping hazard and shall be flush to the floor or removed.
|
9/18/2024
|