Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Car phone does not work. 9/18/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power operation shall be tested, with weights. 9/18/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) x Emergency power jewel needs to be installed at main landing. 9/18/2024
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 x The machine room door is missing most of the fire gasket material. 9/18/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x There is no light switch and no GFI outlet in the machine room. 9/18/2024
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Walls to be of solid construction, fill fire penetrations, cracks, and gaps. 9/18/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x FAID devices to be permanently installed with appropriate covers. 9/18/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Machine room: Overhead water/waste piping not allowed in machine space. 9/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Disconnects need feed location labels. 9/18/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Disconnect to controller "flex" shall not exceed 6ft in length. 9/18/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Hoistway fire penetrations need to be fire caulked. 9/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Secure sump pump cover. 9/18/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 3.8 x Sump outlet shall be a single outlet, not duplex. 9/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall be at least 10fc. 9/18/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Need to test all FAID operations. 9/18/2024