Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Add GFCI outlet at top of hoistway. 10/11/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fill 6" gap at the top landing in hoistway and clean down hoistway. 10/11/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk holes, gaps under sills, & around all beams in hoistway. 10/11/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Heat detector shall be within 24" of sprinkler head. 10/11/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Maximum hoisting capacity needs to be listed on hoisting beam. 10/11/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x Pit ladder is 42" & needs to be 48" above the sill. 10/11/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Plug holes in electrical boxes at the top of hoistway. 10/11/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Relocate heat and smoke detectors from hoisting beam in hoistway to the ceiling of the hoistway. 10/11/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up rescue device was tested and did not operate as designed, the elevator failed to pick the brake as required.. Repair the device to operate as it is designed. Reinspection required. 3/10/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x The pit light shall be operational. 10/11/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x The sump pump is not wired. 10/11/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The emergency power operation and fireman’s service operation shall be tested before the inspection is completed. 3/10/2026
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x There is not enough light in control space. 10/11/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Vent needs to be more than 36" from heat & smoke detector at top landing. 10/11/2024