Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Machine room smoke needs to be moved within 12" of ceiling.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Governor test shall be completed.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x All phases of fire service, including initiating devices, shall be tested.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Possible pinch point on top of elevator in rear due to beams for structure must be addressed somehow, possible facia necessary.