Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x All phases of fire service has to be checked including smokes, heat, and flow valve.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x Counterweight runby shall be a min of 6" and a max of 7".
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Emergency generator test shall be performed.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Verify sump pump is code compliant for a shared hoistway. Code requires the sump pump shall be able to discharge 3000 gallons per hour per elevator.