A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Disconnects shall be labeled with location of feeder breakers.
|
5/31/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
x
|
|
Emergency communications loss monitor shall work.
|
5/31/2024
|
A17.1-2016 : Elevators
|
4.8 - Hoistway enclosure
|
2.1.1
|
x
|
|
Fire caulking: Touch-up fire caulking on non-factory horizontal joints and cracks, around door frames, and at the top of the hoistway where the walls meet the ceiling.
|
5/31/2024
|
A17.1-2016 : Elevators
|
4.8 - Hoistway enclosure
|
2.1.1
|
x
|
|
Hoistway fire penetration seams, gaps, etc to be fire caulked.
|
5/31/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work.
|
5/31/2024
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
2.20.2
|
x
|
|
Verify and provide documentation that suspension means are of fire resistant construction (no sprinklers).
|
5/31/2024
|