Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The top floor of Machine Roomless Elevators are considered a machine space. Provide a fire extinguisher at the top landing near the elevator entrance.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) x The escape hatch safety switch shall be attached to the escape hatch. 2/28/2025
MO Minimum : Elevators (I) - Pits (I)1 There is 6" of standing water in the pit. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
MO Minimum : Elevators (I) - Pits (I)1 The drain provided in the elevator pit does not allow accumulated water to fully drain from the pit. Permanent provisions shall be made to prevent accumulation of groundwater in the pit (see 2.1.2.2).
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Elevators provided with an emergency or standby power system to operate the elevator in case the normal power supply fails shall comply with the requirements of 2.27.2.1 through 2.27.2.5.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator is equipped with emergency power. The operation of elevators equipped with standby or emergency power shall be tested annually to determine conformance with the applicable requirements. 2/28/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x In elevators provided with Firefighters‘ Emergency Operation, a drain or sump pump shall be provided. The sump pump/drain shall have the capacity to remove a minimum of 11.4 m3/h (3,000 gal/h) per elevator. 2/28/2025