A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Pit sump pump is required and shall have the capacity to remove a minimum of 3,000 gal/h per elevator (allowing for head pressure resulting from discharge piping height).
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room lighting shall not be less than 19fc at floor.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Spaces containing machines, control equipment, sheaves, and other machinery shall be separated from the remainder of the building by a fire-resistive enclosure. Seal hoistway holes and penetrations with approved fire resistant material.
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Knockout plugs missing on multiple electrical boxes at the top of the hoistway.
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Top of the hoistway has a "flex" electrial run longer than 6' of continuous run.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Pit sump pump discharge piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating.
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Pit electrical piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating.
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
x
|
|
Disconnects do not meet 30" rule/not co-planer (electrical supply).
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Heat devices did not initiate shunt and smokes did not initiate proper floor recalls or Hat operation.
|
|