Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Spaces containing machines, control equipment, sheaves, and other machinery shall be separated from the remainder of the building by a fire-resistive enclosure. Seal hoistway holes and penetrations with approved fire resistant material.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit sump pump is required and shall have the capacity to remove a minimum of 3,000 gal/h per elevator (allowing for head pressure resulting from discharge piping height).
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit sump pump discharge piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Heat devices did not initiate shunt and smokes did not initiate proper floor recalls or Hat operation.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting shall not be less than 19fc at floor.
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Knockout plugs missing on multiple electrical boxes at the top of the hoistway.
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of the hoistway has a "flex" electrial run longer than 6' of continuous run.
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Pit electrical piping shall be of fire-resistant/non-combustible materials. All materials contained within the hoistway shall meet minimum fire-resistance rating.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 x Disconnects do not meet 30" rule/not co-planer (electrical supply).