Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x A17.1-2016 1.6 CAR EMERGENCY SIGNAL, PHONES NOT WORKING, RE-INSPECTION 2.27.1.1.6 (a) The two-way communications means within the car shall include a means to verify operability of the telephone line. 10/31/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x A17.1-2016 1.17 STANDBY POWER OPERATION NOT WORKING, RE-INSPECTION. 2.27.2 Emergency or Standby Power System Elevators provided with an emergency or standby power system to operate the elevator in case the normal power supply fails shall comply with the requirements of 2.27.2.1 through 2.27.2.5. 10/31/2024
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.3 x x A17.1-2016 6.5 FIREFIGHTER SERVICE NOT OPERATIONAL, RE-INSPECTION REQUIRED 2.27.3 Firefighters’ Emergency Operation: Automatic Elevators NOT OPERABLE 10/31/2024