MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Feeder location needs to be on disconnect.
|
8/16/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
8/16/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
10/10/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The installation of the fire alarm and initiating devices need to be completed and tested.
|
8/16/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The installation of the fire alarm and initiating devices need to be completed and tested.
|
10/10/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
x
|
|
NEC 110.26a - Provide code compliant spacing of disconnects in the machine room.
|
10/10/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
x
|
|
NEC 110.26a - Provide code compliant spacing of disconnects in the machine room.
|
8/16/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Outlets in machine room need to be GFCI.
|
8/16/2024
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
Machine room needs to be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator equipment manufacturer.
|
8/16/2024
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Missing fire extinguisher.
|
8/16/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Wires in machine room are exposed.
|
8/16/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
NEC - The breaker shall be sized properly for the wire size.
|
8/16/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
NEC - The breaker shall be sized properly for the wire size.
|
10/10/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Remove screws in ceiling at the top of the hoistway.
|
10/10/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fire caulk gap in walls, door jams & around beam in hoistway.
|
10/10/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Remove screw in ceiling at the top of the hoistway.
|
8/16/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fire caulk gap in walls, door jams & around beam in hoistway.
|
8/16/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Wiring in pit needs to be in conduit. Sump pump wiring running over 6 feet in length shall be enclosed in conduit.
|
8/16/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Remove single non GFI outlet in pit.
|
8/16/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Relocate GFCI in pit to an accessible location.
|
8/16/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Relocate GFCI in pit to an accessible location.
|
10/10/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
x
|
|
Wires behind ladder need to be in conduit & relocated. 4.5" of clearance from the center line of the ladder rungs to the wall shall be provided.
|
10/10/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Provide lighting to obtain a minimum of 10 foot candles on all areas of the pit floor.
|
8/16/2024
|