Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The installation of the fire alarm and initiating devices need to be completed and tested. 8/16/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The installation of the fire alarm and initiating devices need to be completed and tested. 10/10/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Remove screw in ceiling at the top of the hoistway. 8/16/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Fire caulk gap in walls, door jams & around beam in hoistway. 8/16/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Remove screws in ceiling at the top of the hoistway. 10/10/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Fire caulk gap in walls, door jams & around beam in hoistway. 10/10/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Yes No Wires behind ladder need to be in conduit & relocated. 4.5" of clearance from the center line of the ladder rungs to the wall shall be provided. 10/10/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No Provide lighting to obtain a minimum of 10 foot candles on all areas of the pit floor. 8/16/2024
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 Yes No Machine room needs to be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator equipment manufacturer. 8/16/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No NEC - The breaker shall be sized properly for the wire size. 10/10/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Relocate GFCI in pit to an accessible location. 10/10/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Wiring in pit needs to be in conduit. Sump pump wiring running over 6 feet in length shall be enclosed in conduit. 8/16/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Remove single non GFI outlet in pit. 8/16/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Relocate GFCI in pit to an accessible location. 8/16/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No Wires in machine room are exposed. 8/16/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No Outlets in machine room need to be GFCI. 8/16/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 Yes No NEC - The breaker shall be sized properly for the wire size. 8/16/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 Yes No NEC 110.26a - Provide code compliant spacing of disconnects in the machine room. 8/16/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 Yes No NEC 110.26a - Provide code compliant spacing of disconnects in the machine room. 10/10/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No In cab emergency telephone does not work and shall be repaired and tested. 9/18/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 10/10/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 8/16/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No Missing fire extinguisher. 8/16/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Yes No Feeder location needs to be on disconnect. 8/16/2024