Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 8/16/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 10/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Feeder location needs to be on disconnect. 8/16/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk gap in walls, door jams & around beam in hoistway. 8/16/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk gap in walls, door jams & around beam in hoistway. 10/10/2024
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Machine room needs to be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator equipment manufacturer. 8/16/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Missing fire extinguisher. 8/16/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x NEC - The breaker shall be sized properly for the wire size. 8/16/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x NEC - The breaker shall be sized properly for the wire size. 10/10/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 x NEC 110.26a - Provide code compliant spacing of disconnects in the machine room. 10/10/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 x NEC 110.26a - Provide code compliant spacing of disconnects in the machine room. 8/16/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Outlets in machine room need to be GFCI. 8/16/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Provide lighting to obtain a minimum of 10 foot candles on all areas of the pit floor. 8/16/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Relocate GFCI in pit to an accessible location. 8/16/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Relocate GFCI in pit to an accessible location. 10/10/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Remove screw in ceiling at the top of the hoistway. 8/16/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Remove screws in ceiling at the top of the hoistway. 10/10/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Remove single non GFI outlet in pit. 8/16/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The installation of the fire alarm and initiating devices need to be completed and tested. 10/10/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The installation of the fire alarm and initiating devices need to be completed and tested. 8/16/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x Wires behind ladder need to be in conduit & relocated. 4.5" of clearance from the center line of the ladder rungs to the wall shall be provided. 10/10/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Wires in machine room are exposed. 8/16/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Wiring in pit needs to be in conduit. Sump pump wiring running over 6 feet in length shall be enclosed in conduit. 8/16/2024