Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication in car shall work. 2/28/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Rescue communications system (7th floor) to be tested. 2/28/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space lighting at 8th landing shall be at least 19fc. 2/28/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fill fire/smoke penetrations with appropriate fire rated caulking. 2/28/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway - wire-way cut/damaged. Repair/replace. 2/28/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway - Multiple knockout plugs missing. 2/28/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway - GFI not working. 2/28/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Hoistway - 4x4 electrical box missing cover. 2/28/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Sump cover is too small and does not completely cover sump hole. 2/28/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.4 x Sump outlet shall be a dedicated simplex outlet. 2/28/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Pit heat detector shall not be less than 48" from pit floor or remove. 2/28/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Smoke/heat detectors shall be at least 3 feet from HVAC register. 2/28/2025
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 x 2.11.6.3 - Landing smoke doors shall work and be tested with FAID. 2/28/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x All elevator FAID to be tested. 2/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x "In case of fire" signage missing. Permanently install at all floors. 2/28/2025