Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | x | All electric wiring in pit at 48" and below must be NEMA 4 (water tight). | ||
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting must be 19 footcandles. It is currently at 8 footcandles. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Machine room door needs "low clearance" sign. |