Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting must be 19 footcandles. It is currently at 8 footcandles.
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x All electric wiring in pit at 48" and below must be NEMA 4 (water tight).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Machine room door needs "low clearance" sign.