Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Video/text is not working. There is no internet. 11/18/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space lighting at 4th landing is less than 19fc. 11/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Disconnects need to have feeder locations labeled. 11/18/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistway penetrations improperly sealed with non-fire rated caulk. Remove and re-caulk with appropriate fire-rated sealant. 11/18/2024
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Smoke curtain at 4th landing has faulty battery. 11/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit sump pump is not wired/working. 11/18/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Pit sump pump discharge piping is within counterweight running space; relocate. 11/18/2024