Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No the emergency light came on but the alarm bell did not work 6/13/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 No No Both front and rear door close force needs to be adjusted so that the pressure is less than 30lbs
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Both front and rear door restrictors are not working, repair door restrictors 8/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency lights did not come on, repair it so the emergency lights work 8/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No machine room fire extinguisher needs to be recharged, the gauge is on zero it has been discharged, inspection tag is from 2015
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No both the front and rear door restrictors need to be adjusted so they work 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No could not get the seismic to trip, provide written instruction in the machine room with the seismic testing procedures
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No fire service phase 1 keyswitch collar markings can no longer be read, replace keyswitch collar (2.27.3.1.1(b)) [non red tag]
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room fire extinguisher inspection tag is from 2013, have the fire extinguisher inspected and tagged annually
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Fire service phase 1 keyswitch collar markings can no longer be read, replace collar
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No fire service phase 2 would not close the door to run the elevator, the door was bouncing on the open limit 6/13/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No perform monthly fire service test and post log in the machine room
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No both front and rear door restrictors are not working, adjust and repair door restrictors 6/4/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No machine room fire extinguisher inspection tag is expired from 2013, have the fire extinguisher inspected and tagged annually
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Update expired fire extinguisher
conversion conversion n/a No No repair both the front and rear car door restrictors neither are working 10/25/2019
conversion conversion n/a No No fire extinguisher is to be inspected and tagged annually, tag is from 2015 10/25/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. The one in the machine room is from 2015.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually.